How the conversions work
Every unit is stored as a factor to one SI base unit: m³/s for flow, Pa for pressure, W for power and so on. To convert, the calculator divides the From unit's factor by the To unit's factor and multiplies your value by the result. The math panel shows each step, so you can check the factor or copy it into a PLC scaling routine.
Temperature is the exception, because the scales have different zero points. °F to °C, for example, is (°F − 32) × 5/9, not a single factor. For a temperature change, such as a heat exchanger's W/K rating or a 10 °F rise, use the Temperature difference quantity: a change of 1 °C equals a change of 1 K or 1.8 °F, with no offset.
Conversions controls engineers use most
| From | To | Multiply by |
|---|---|---|
| GPM (US) | L/min | 3.78541 |
| GPM (US) | m³/h | 0.227125 |
| CFM | m³/h | 1.69901 |
| psi | bar | 0.0689476 |
| psi | kPa | 6.89476 |
| inH₂O | Pa | 249.089 |
| HP | kW | 0.745700 |
| ft/min | m/min | 0.3048 |
| lb·ft | N·m | 1.35582 |
| lb/ft³ | kg/m³ | 16.0185 |
| W | BTU/h | 3.41214 |
| kcmil | mm² | 0.506707 |
Notes on units that trip people up
- Gallons: GPM here means US gallons. An imperial gallon is about 20% larger, so pick "Imperial gal/min" for UK equipment.
- Water column: inH₂O and ftH₂O use the conventional value (water at about 4 °C). Some instruments use 60 °F or 68 °F water, which differs by about 0.1–0.2%.
- Gauge and absolute: psig and psia convert the same way. The difference is the reference point, roughly 14.7 psi of atmosphere at sea level, which a unit conversion does not add or remove.
- Rotational speed: rev/s is labeled Hz here, which is not the same as the drive's output frequency. Motor shaft speed also depends on pole count and slip.
Frequently asked questions
How do I convert GPM to L/min?
Multiply US gallons per minute by 3.78541. For example, 100 GPM is 378.5 L/min.
How do I convert psi to bar?
Multiply psi by 0.0689476, or divide by 14.5038. For example, 100 psi is 6.895 bar.
How do I convert HP to kW?
Multiply mechanical horsepower by 0.7457. For example, 10 HP is 7.457 kW.
What is the difference between a temperature and a temperature difference?
A temperature conversion includes the offset between scales, so 0 °C is 32 °F. A temperature difference has no offset: a change of 1 °C equals a change of 1.8 °F. Use temperature difference for ratings such as W/K or for a temperature rise.