Why the same 4–20 mA signal reads differently on every card
Each Allen-Bradley analog family turns the signal into a number its own way, so a count that's right for one card is wrong for another. The same 4–20 mA signal shows up as:
| Module | Format | 4 mA | 20 mA |
|---|---|---|---|
| 1746-NI4 (SLC) | Integer | 3,277 | 16,384 |
| 1746-NO4I (SLC) | Integer | 6,242 | 31,208 |
| 1762-IF2OF2 | Raw/Proportional | 6,240 | 31,200 |
| 1769-IF4 / IF8 | Engineering Units | 4,000 | 20,000 |
| 1769-IF4 / IF8 | Scaled-for-PID | 0 | 16,383 |
| 1734-IE2C (POINT) | Default scaling | 3,277 | 16,383 |
| 1794-IE8 (FLEX) | 4–20 mA mode | 0 | 30,840 |
| 1756-IF16 (ControlLogix) | Integer mode | −20,030 | 30,920 |
Tips
- Check one channel with a loop calibrator before trusting raw counts in a new design, especially where a card shows a caution note.
- Watch the module's over- and under-range limits. Most 4–20 mA ranges report down to about 3.2 mA or 0 mA and up to about 21 mA; a broken wire usually reads at or below the low limit and sets the under-range bit.
- Prefer floating point on Logix chassis I/O. 1756 and 5069 modules can scale on the module, so the tag already reads in engineering units and the counts question goes away.
Frequently asked questions
What is 4 mA on a 1746-NI4?
3,277 counts, and 20 mA is 16,384. The NI4 scales ±20 mA to ±16,384 regardless of the range you use.
What is 4-20 mA on a 1769-IF4 in Engineering Units?
4,000 to 20,000. In Scaled-for-PID it is 0 to 16,383, and in Percent Range 0 to 10,000.
Why does my 1794-IE8 read 30840 at 20 mA?
In 4-20 mA mode the FLEX analog modules put 4 mA at 0 and 20 mA at 30,840 (7878 hex); 32,767 is 21 mA.
What are the 1756-IF16 integer counts for 4-20 mA?
In integer mode the IF16 has no 4-20 mA range; on 0-20 mA the current manual puts 0 mA at -32,768 and 20.58 mA at 32,767, so 4 mA is about -20,030 and 20 mA about 30,920. The 1756-IF6I reads -20,341 at 4 mA.